Cooling Water Circulator (Externally Closed Circulation, Air Cooling) (CFA302)

Cooling Water Circulator (Externally Closed Circulation, Air Cooling) (CFA302)

Description

Precision external closed cooling water circulator with the temp. control accuracy±0.1°C.

Features of Cooling Water Circulator (Externally Closed Circulation, Air Cooling) (CFA302)

Features
Provide high-precision circulatin water with the temp. range -10°C+80°C (CFA611/CFW611) and temp. control accuracy±0.1°C.
Features
Powerful cooling capacity.
Features
Continuous monitoring for water level, abnormal refrigerator pressure, refrigerator operation, circulation pump operation, etc..
Features
Configurated with auto stop, auto start operations, temp. output terminal, deviation correction, external communication (RS485), etc..
Safety Features
Overcurrent ELB, self-diagnosis, key lock, refrigerator overload protector, refrigerator delay timer of protection, refrigerator pressure detection, float switch preventing pump idling, bypass for protecting circulating pump, auto overheat protection, overheat protector, etc..

Additional information

Model

CFA302

Circulating pump

Magnetic drive pump 45W

Weight

60kg

Method

External closed circulation

Operating temperature range

-10 to +60°C

Temperature control accuracy

±0.1°C JTM K05 (at 20°C)

Temperature setting, display

attribute:Digital Setting and Display

Temperature indicating unit

0.1°C

Cooling capacity

Approx. 370W (318Kcal/h), at fluid temp.10°C

Operating environmental temp. range

5 to 35°C

Temperature control

PID control

Temperature sensor

Temp. controller: Pt thermal resistance, overheat protection: K thermocouple

Refrigerator, refrigerant

Air cooling 300W, R404A

Item Code

221348

Unit circulation ability (50/60Hz) Max. lift, Pump capacity

6.6 / 9.0m (8.0 / 11.0m)

Unit circulation ability (50/60Hz) Max. flow, Pump capacity

8.9 / 10.3L/min (15 / 17L/min)

Heater

Stainless steel heater 850W

Cooling coil

Nickel-clad copper

External circulation nozzle

Rc3/8 (CFA301 standard configuration pagoda connector)

Safety device

Overcurrent ELB, Self-diagnosis, Refrigerator overload protector, Refrigerator delay timer of protection, Refrigerator pressure detection, Float switch preventing pump idling,

Safety device 2

Bypass for protecting circulating pump, Auto overheat protection, Overheat protector, etc..

Other functions

Drain valve, Condenser filter screen, Deviation correction, External communication (RS485), Refrigerator pressure indicator, Key lock, Temp. output terminal

Accessories

Drain pipe, Overflow pipe

External dimensions(W×D×H mm)

380×565×725mm

Remarks(dimensions)

Bath capacity 13L, W245×D315×H180mm

Power Source

AC115V/AC220V
Single-phase with step down transformer